[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931812":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},931812,604,1,"单选题","（2019年真题）某电信楼共有6个通讯机房,室内净高均为4. 5m,通讯机房设置了组合分配式七氟丙烷灭火系统，该灭火系统的下列设计方案中，错误的是()",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","喷头安装高度为4m,喷头保护半径为8m",true,{"key":16,"text":17,"correct":18},"B","设计喷放时间为7s",false,{"key":20,"text":21,"correct":18},"C","6个防护区由-套组合分配系统保护",{"key":23,"text":24,"correct":18},"D","集流管和储存容器上设置安全泄压装置","P298-307 根据《气体灭火系统设计规范》（GB50370-2005）中第3.1.12 规定，喷头的保护高度和保护半径，应符合下列规定： 1 最大保护高度不宜大于6.5m； 2 最小保护高度不应小于0.3 m； 3 喷头安装高度小于1.5 m时，保护半径不宜大于4.5 m； 4 喷头安装高度不小于1.5m时，保护半径不应大于7.5 m。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]