[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931799":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931799,604,1,"单选题","（2015真题）某5层数据计算机房，层高5m，每层有1200m2的大空间计算机用房，设置IG541组合分配气体灭火系统保护。该建筑的气体灭火系统防护区最少应划分为（）个。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","5",false,{"key":16,"text":17,"correct":14},"B","6",{"key":19,"text":20,"correct":14},"C","8",{"key":22,"text":23,"correct":24},"D","10",true,"气体灭火防护区宜以单个封闭空间划分，采用管网灭火系统时，一个防护区的面积不宜大于800m2，且容积不宜大于3600m3。因此按面积计算，单层防护区个数=1200÷800=1．5（个），取2个，5层应设防护区共10个；按体积计算，单层防护区个数为（1200×5）÷3600=1．7（个），取2个，5层应设防护区共10个。综合面积和容积两个方面因素，该建筑的气体灭火系统防护区最少应划分为10个。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]