[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931797":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931797,604,1,"单选题","(2018年) 某电子计算机房，拟釆用气体灭火系统保护，下列气体灭火系统中，设计灭火浓度最低的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","氮气灭火系统",false,{"key":16,"text":17,"correct":14},"B","IG541灭火系统",{"key":19,"text":20,"correct":14},"C","二氧化碳灭火系统",{"key":22,"text":23,"correct":24},"D","七氟丙烷灭火系统",true,"二氧化碳设计浓度不应小于灭火浓度的1.7倍，并不得低于34%，七氟丙烷灭火系统的灭火设计浓度不应小于灭火浓度的1.3倍，惰化设计浓度不应小于惰化浓度的1.1倍。固体表面火灾的灭火浓度为5.8% ，设计规范中未列出的，应经试验确定。图书、档案、票据和文物资料库等防护区，灭火设计浓度宜采用10% 。油浸变压器室、带油开关的配电室和自备发电机房等防护区，灭火设计浓度宜采用9% ，通信机房和电子计算机房等防护区，灭火设计浓度宜采用8% 。防护区实际应用浓度不应大于灭火设计浓度的1.1倍。IG-5411昆合气体灭火系统的灭火设计浓度不应小于灭火浓度的1.3倍，惰化设计浓度不应小灭火浓度的1.1倍。固体表面火灾的灭火浓度为28.1%，规范中未列出的，应经试验确定。P293-296",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]