[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931786":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931786,604,1,"单选题","（2016真题）下列关于水喷雾灭火系统水雾喷头选型和设置要求的说法中，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","扑救电气火灾应选用离心雾化型水雾喷头",false,{"key":16,"text":17,"correct":14},"B","室内散发粉尘的场所设置的水雾喷头应带防尘帽",{"key":19,"text":20,"correct":14},"C","保护可燃气体储罐时，水雾喷头距离保护储罐外壁不应大于0.7m",{"key":22,"text":23,"correct":24},"D","保护油浸式变压器时，水雾喷头之间的水平距离与垂直距离不应大于1.2m",true,"离心雾化型水雾喷头形成的水雾具有良好的电绝缘性，适合扑救电气火灾，选项A正确。保护对象为油浸式变压器时，水雾喷头之间的水平距离与垂直距离应满足水锥相交的要求，选项D错误。当保护对象为可燃气体和甲、乙、丙类液体储罐时，水雾喷头宜布置在保护对象周围，其与保护储罐外壁之间的距离不应大于0．7m，选项C正确。根据《水喷雾灭火系统技术规范》（GB50219）的规定，室内粉尘场所设置的水雾喷头应带防尘帽，室外设置的水雾喷头宜带防尘帽，选项B正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]