[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931759":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931759,604,2,"多选题","（2018真题）下列民用建筑（场所）自动喷水灭火系统参数设计方案中，正确的有（ ）。 {图}",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","方案 4",false,{"key":16,"text":17,"correct":14},"B","方案 5",{"key":19,"text":20,"correct":21},"C","方案 1",true,{"key":23,"text":24,"correct":21},"D","方案 2",{"key":26,"text":27,"correct":21},"E","方案 3","CDE","据《自动喷水灭火系统设计规范》(GB50084-2017)附录A设置场所火灾危险等级分类和第5.0.1条民用建筑和厂房采用湿式系统时的设计基本参数,高层办公室属于中危险I级,方案1正确;地下汽车库属于中危险Ⅱ级,方案2正确。第5.0.2条,民用建筑和厂房高大空间场所采用湿式系统的设计基本参数不应低于表5.0.2的规定,方案3正确方案4、方案5错误。 5.0.1民用建筑和厂房采用湿式系统时的设计基本参数不应低于表5.0.1的规定",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]