[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931744":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},931744,604,1,"单选题","（2015真题）设置湿式自动喷水灭火系统的房间，起火时喷头动作喷水，水流指示器动作并报警，报警阀动作，延迟器充水，启泵装置动作报警并直接启动消防水泵，该系统应选择的启泵装置是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","压力开关",true,{"key":16,"text":17,"correct":18},"B","电接点压力表",false,{"key":20,"text":21,"correct":18},"C","流量开关",{"key":23,"text":24,"correct":18},"D","水位仪","湿式系统在准工作状态时，由消防水箱或稳压泵、气压给水设备等稳压设施维持管道内充水的压力。发生火灾时，在火灾温度的作用下，闭式喷头的热敏元件动作，喷头开启并开始喷水。此时，管网中的水由静止变为流动．水流指示器动作送出电信号，在报警控制器上显示某一区域喷水的信息。由于持续喷水泄压造成湿式报警阀的上部水压低于下部水压，在压力差的作用下，原来处于关闭状态的湿式报警阀将自动开启。此时，压力水通过湿式报警阀流向管网，同时打开通向水力警铃的通道，延迟器充满水后，水力警铃发出声响警报，压力开关动作并输出启动供水泵的信号。供水泵投入运行后，完成系统的启动过程。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]