[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931742":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},931742,604,1,"单选题","（2016真题）下列关于干式自动喷水灭火系统的说法中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","在准工作状态下，由稳压系统维持干式报警阀入口前管道内的充水压力",false,{"key":16,"text":17,"correct":14},"B","在准工作状态下，干式报警阀出口后的配水管道内应充满有压气体",{"key":19,"text":20,"correct":21},"C","当发生火灾后，干式报警阀开启，压力开关动作后管网开始排气充水",true,{"key":23,"text":24,"correct":14},"D","当发生火灾后，配水管道排气充水后，开启的喷头开始喷水","干式系统在准工作状态时，由消防水箱或稳压泵、气压给水设备等稳压设施维持干式报警阀人口前管道内的充水压力，报警阀出口后的管道内充满有压气体（通常采用压缩空气），报警阀处于关闭状态。发生火灾时，在火灾温度的作用下，闭式喷头的热敏元件动作，闭式喷头开启，使干式阀的出口压力下降，加速器动作后促使干式报警阀迅速开启，管道开始排气充水，剩余压缩空气从系统最高处的排气阀和开启的喷头处喷出。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]