[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931740":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},931740,604,1,"单选题","（2015真题）在环境温度低于4℃的地区，建设一座地下车库，采用干式自动喷水灭火系统保护，系统的设计参数按照火灾危险等级的中危险级Ⅱ级确定，其作用面积不应小于（ ）m2。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","160",false,{"key":16,"text":17,"correct":18},"B","208",true,{"key":20,"text":21,"correct":14},"C","192",{"key":23,"text":24,"correct":14},"D","260","对于民用建筑和工业厂房，系统设计基本参数应符合表3-3-2的要求。仅在走道设置单排闭式喷头的闭式系统，其作用面积应按最大疏散距离所对应的走道面积确定；在装有网格、栅板类通透性吊顶的场所，系统的喷水强度应按表3-3-2规定值的1.3倍确定；干式系统的作用面积按表3-3-2规定值的1.3倍确定。系统最不利点处喷头的工作压力不应低于0. 05MPa。@##",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]