[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931733":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931733,604,2,"多选题","（2016真题）某高层建筑，建筑高度50m，设有3台湿式报警阀。下列关于末端试水装置设置的说法中，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","每层最不利点喷头处均应设施末端试水设置",false,{"key":16,"text":17,"correct":14},"B","末端试水装置的出流量应由系统流量系数最大的喷头确定",{"key":19,"text":20,"correct":21},"C","末端试水装置应由试水阀、压力表、试水接头组成",true,{"key":23,"text":24,"correct":21},"D","末端试水装置的出水应采取孔口出流的方式排入排水管道",{"key":26,"text":27,"correct":21},"E","末端试水装置处排水管道的直径不宜小于DN75","CDE","",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]