[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931729":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},931729,604,1,"单选题","（2020年真题）下列场所中，应设置消防洒水软管或轻便消防水龙的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","建筑高度为30m的丙类厂房",false,{"key":16,"text":17,"correct":18},"B","建筑高度为24m的商场",true,{"key":20,"text":21,"correct":14},"C","建筑高度为28m的住宅",{"key":23,"text":24,"correct":14},"D","建筑面积为180㎡的商业服务网点","P277-283 下列建筑中，可不设置室内消火栓系统，但宜设置消防软管卷盘或轻便消防水龙： 1耐火等级为一、二级且可燃物较少的单、多层丁、戊类厂房（仓库）。 2耐火等级为三、四级且建筑体积不大于3000m3的丁类厂房；耐火等级为三、四级且建筑体积不大于5000m3的戊类厂房（仓库）。 人员密集的公共建筑、建筑高度大于100m的建筑和建筑面积大于200m2的商业服务网点内应设置消防软管卷盘或轻便消防水龙。高层住宅建筑的户内宜配置轻便消防水龙。 B属于人员密集场所。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]