[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931726":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},931726,604,1,"单选题","（2020年真题）某酒店室内消火栓系统的设计工作压力为1.0MPa，设置2台消火栓泵（一用一备），消火栓泵出水管上压力表最大量程至少应为（ ）MPa。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","2.5",true,{"key":16,"text":17,"correct":18},"B","0.5",false,{"key":20,"text":21,"correct":18},"C","1.0",{"key":23,"text":24,"correct":18},"D","1.6","P258-275 消防水泵出水管压力表的最大量程不应低于其设计工作压力的2倍，且不应低于1.60MPa。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]