[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931725":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},931725,604,1,"单选题","（2019年真题）某6层宾馆，建筑高度为23m,建筑体积26000m3。设有消火栓系统和自动喷水灭火系统。该宾馆室外消火栓设计流量为30L\u002Fs, 室内消火栓设计流量为20L\u002Fs，自动喷水灭火系统设计流量为20L\u002Fs。 按上述涉及参数，该宾馆一次火灾的室内外消防用水量为（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","504m3",false,{"key":16,"text":17,"correct":18},"B","432m3",true,{"key":20,"text":21,"correct":14},"C","522m3",{"key":23,"text":24,"correct":14},"D","612m3","P220-231 题目中建筑为多层公共建筑，计算消火栓用水量时，火灾延续时间按2h计算；除另有特殊规定外，自动喷水灭火系统的持续喷水时间应按火灾延续时间不小于1h确定。 室内消火栓消防用水量为20L\u002Fs*2*3.6=144m3； 室外消火栓消防用水量为30L\u002Fs*2*3.6=216m3； 自动喷水灭火系统消防用水量为20L\u002Fs*1*3.6=72m3； 故，一次火灾的室内外消防用水量为144+216+72=432m3。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]