[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931719":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931719,604,2,"多选题","（2019年真题）某办公楼地上8层，建筑高度32m，室内消火栓采用临时高压消防给水系统，并设有稳压泵。该消防给水系统稳压泵的下列设计方案中，正确的有（）",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","稳压泵不设置备用泵",false,{"key":16,"text":17,"correct":18},"B","稳压泵的设计流量不小于室内消火栓系统管网的正常液漏量和系统自动启动流量",true,{"key":20,"text":21,"correct":18},"C","稳压泵采用单吸多级离心泵",{"key":23,"text":24,"correct":14},"D","稳压泵的设计压力保持系统最不利点处室内消火栓在准工作状态时的静水压力为0.10MPa",{"key":26,"text":27,"correct":18},"E","稳压泵叶轮材质采用不锈钢","BCE","P201-213 消防稳压泵应设置备用泵，通常可按“用一备一”的原则选用，宜采用单吸单级或单吸多级离心泵，泵外壳和叶轮等主要部件的材质宜采用不锈钢。故A选项说法不正确，C、E选项说法正确。 消防给水系统消防稳压泵的设计流量不应小于消防给水系统管网的正常泄露量和系统自动启动流量。当没有管网泄漏量数据时，稳压泵的设计流量宜按消防给水设计流量的1%~3%计，且不宜小于1L\u002Fs。故B选项说法正确 稳压泵的设计压力应保持系统最不利点处水灭火设施在准工作状态时的静水压力大于0.15MPa。故D选项说法不正确",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]