[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931717":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931717,604,2,"多选题","（2018真题）某多层科研楼设有室内消防给水系统，其高位消防水箱进水管管径为 DN100。该高位消防水箱溢流管的下列设置方案中，正确的有()。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","溢流水管经排水沟与建筑排水管网连接",true,{"key":16,"text":17,"correct":18},"B","溢流水管上安装用于检修的闸阀",false,{"key":20,"text":21,"correct":18},"C","溢流管采用 DN150 的钢管",{"key":23,"text":24,"correct":18},"D","溢流管的喇叭口直径为 250mm",{"key":26,"text":27,"correct":14},"E","溢流水位低于进水管口的最低点 100mm","AE","根据《自动噴水灭火系统施工及验收規范》(GB50261)第4.3.4条,消防水池,高位消防水箱的溢流管、泄水管不得与生产或生活用水的排水系统直接相连,应采用间接排水方式。溢流管的直径不应小于进水管直径的2倍,且不应小于DN100,C错误;溢流管的喇叭口直径不应小于溢流管直径的1.5-2.5倍,D错误。根据第52.6条,高位消防水箱进水管应在溢流水位以上接入,进水管口的最低点高出溢流边缘的高度应等于进水管管径,但最小不应小于100mm,最大不应大于150mm,E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]