[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931715":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931715,604,1,"单选题","（2017真题）单台消防水泵的设计压力和流量分别不大于（ ）时，消防泵组应在泵房内预留流量计和压力计接口。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","0.50MPa、25L\u002Fs",false,{"key":16,"text":17,"correct":14},"B","1.00MPa、25L\u002Fs",{"key":19,"text":20,"correct":14},"C","1.00MPa、20L\u002Fs",{"key":22,"text":23,"correct":24},"D","0.50MPa、20L\u002Fs",true,"《消规》5.1.11一组消防水泵应在消防水泵房内设置流量和压力测试装置,并应符合下列规定： 单台消防水泵的流量不大于20L\u002Fs、设计工作压力不大于0.50MPa时，泵组应预留测量用流量计和压力计接口，其他泵组宜设置泵组流量和压力测试装置；",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]