[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931697":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},931697,604,1,"单选题","（2015真题）某高层办公楼，建筑高度为32m，内走廊为“一”字形，设置两座防烟楼梯间，其前室入口的中心线间距为15m，走廊两端的袋形走道长度为3m,走廊两侧房间进深均为6m。该办公楼每层设置的室内消火栓竖管数量不应少于（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":18},"B","2",true,{"key":20,"text":21,"correct":14},"C","3",{"key":23,"text":24,"correct":14},"D","4","根据《消防给水及消火栓系统技术规范》（GB50974—2014）表3．5．2规定，建筑物室内消火栓设计流量见表1．3-9。 {图} 由表1．3-9可知，该办公楼每层设置的消火栓竖管数量不应少于2个，同时使用的消防水枪不少于4支，每个消火栓配置2支消防水枪。对于本题，配置2个消火栓后，按照最不利考虑；任一一个消火栓到房间最远点行走距离为27m，可满足要求。因此，本题的正确答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]