[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931695":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},931695,604,1,"单选题","（2015真题）某商业建筑，东西长为100m、南北宽为60m、建筑高度26m，室外消火栓设计流量为40L\u002Fs，南侧布置消防扑救面。沿该建筑南侧消防扑救面设置的室外消火栓数量，不应少于（ ）个。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":18},"B","3",true,{"key":20,"text":21,"correct":14},"C","4",{"key":23,"text":24,"correct":14},"D","2","室外消火栓的设置要求规定，室外消火栓的数量应按其保护半径和室外消防用水量等综合计算确定，每个室外消火栓的用水量应按10～15L\u002Fs计算；与保护对象之间的距离在5～40m范围内的市政消火栓，可计入室外消火栓的数量内。本题中，该商业建筑室外消火栓设计流量为40L\u002Fs，每个室外消火栓的用水量应按10～15L\u002Fs计算，则建筑南侧消防扑救面设置的室外消火栓数量为3个。@##",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]