[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931694":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931694,604,2,"多选题","（2017真题）关于消防水泵控制的说法，正确的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消防水泵出水干管上设置的压力开关应能控制消防水泵的启动",true,{"key":16,"text":17,"correct":18},"B","消防水泵出水干管上设置的压力开关应能控制消防水泵的停止",false,{"key":20,"text":21,"correct":14},"C","消防控制室应能控制消防水泵启动",{"key":23,"text":24,"correct":14},"D","消防水泵控制柜应能控制消防水泵启动，停止",{"key":26,"text":27,"correct":18},"E","手动火灾报警按钮信号应能直接启动消防水泵","ACD","消防水泵只能人工停泵，不能由压力开关控制消防水泵停止，故B错误，水泵控制柜的停止按钮可以使水泵停止，故D正确；手动火灾报警按钮信号只传递报警信号，不能直接启动水泵，故E错误。@##",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]