[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-928692":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},928692,600,1,"单选题","剪力墙约束边缘构件YBZ1配筋如图 （C）所示，已知墙肢底截面的轴压比为0.4。试问，图中YBZ1有几处违反规范的抗震构造要求，并简述理由。（ ） 提示：YBZ1阴影区和非阴影区的箍筋和拉筋体积配箍率满足规范要求。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","无违反",false,{"key":16,"text":17,"correct":14},"B","有一处",{"key":19,"text":20,"correct":21},"C","有二处",true,{"key":23,"text":24,"correct":14},"D","有三处","该构建的配筋违反以下规范的抗震构造要求： ①YBZ1阴影部分纵向钢筋面积为：As=16×314=5024mm^2＜0.012As=0.012×（800^2－400^2）=5760mm^2，故其违反《混凝土结构设计规范》（GB 50010—2010）第11.7.18条的规定，剪力墙约束边缘构件的纵向钢筋截面面积，一级抗震等级不应小于图中阴影部分面积的1.2％。 ②YBZ1沿长向墙肢长度1100mm＜0.15=0.15×（7500+400）=1185mm，故其违反《混凝土结构设计规范》（GB 50010—2010）表11.7.18的规定，约束边缘构件YBZ1沿长向最小墙肢长度：lc，min=0.15hw=0.15×（7500+400）=1185mm。 综上所述，一共有二处违反规范。",{"id":6,"name":27,"category":28,"favorite":29},"(结构) 专业考试一级","建筑工程",0]