[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-928137":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},928137,599,1,"单选题","非抗震设防区某四层教学楼局部平面如图所示。各层平面布置相同，各层层高均为3.6m。楼、屋盖均为现浇钢筋混凝土板，静力计算方案为刚性方案。墙体为网状配筋砖砌体，采用MU10级烧结普通砖，M10级水泥砂浆砌筑，钢筋网采用乙级冷拔低碳钢丝 方格钢筋网间距为40mm，网的竖向间距130mm。纵横墙厚度均为240mm，砌体施工质量控制等级为B级。第二层窗间墙A的轴向力偏心距e=24mm。[2012年真题] 1.试问，第二层窗间墙A的网状配筋砖砌体受压构件的稳定系数 与下列何项数值最为接近？（ ） 提示：房屋横墙间距s=10800mm。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.45",false,{"key":16,"text":17,"correct":18},"B","0.55",true,{"key":20,"text":21,"correct":14},"C","0.65",{"key":23,"text":24,"correct":14},"D","0.75","根据《砌体结构设计规范》（GB 50005—2011）附录D第D.0.2条规定，网状配筋砖砌体受压构件的稳定系数按下式计算， 根据第8.1.2条式（8.1.2-3）计算，体积配筋百分率为： 根据表5.1.3可知，由于横墙间距：s=10800mm＞2H=2×3600=7200mm，又由于静力计算方案为刚性方案，则墙体的计算高度：H0=1.0H=3600mm； 又根据第5.1.2条式（5.1.2-1）计算，构件高厚比为： 将数据代入 式，可得：稳定系数为： 由此可知，B项数值最为接近。",{"id":6,"name":27,"category":28,"favorite":29},"(结构) 专业考试二级","建筑工程",0]