[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-922195":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},922195,595,1,"单选题","下列对配变电所的设置要求中，( )是错误的。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","-类高层、低层主体建筑内，严禁设置装有可燃性油的设备",false,{"key":16,"text":17,"correct":14},"B","高层建筑中配变电所宜划为单独的防火分区",{"key":19,"text":20,"correct":21},"C","高、低压配电设备不可设在同一房间内",true,{"key":23,"text":24,"correct":14},"D","值班室应单独设置，但可与控制室或低压配电室合并兼用","当高压开关柜的数量为5台及以下时，可和低压配电屏装设在同一房间内。",{"id":6,"name":27,"category":28,"favorite":7},"建筑结构与设备","建筑工程"]