[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-903448":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},903448,584,1,"单选题","下列关于高低压开关柜、配电箱（盘）安装要求说法正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","箱、盘安装应牢固，底边距地面为1.0m",false,{"key":16,"text":17,"correct":18},"B","馈电线路线间绝缘电阻值必须大于0.5MΩ",true,{"key":20,"text":21,"correct":14},"C","柜、箱、盘安装垂直度允许偏差为0.10%",{"key":23,"text":24,"correct":14},"D","基础型钢安装直线度和水平度应小于5mm\u002Fm","高低压开关柜、配电箱（盘）的安装要求包括：①柜、盘、箱的金属柜架及基础型钢必须接地（PE）或接零（PEN）可靠。②基础型钢安装直线度和水平度应小于1mm\u002Fm，全长应小于5mm，位置误差及平行度小于5mm。③柜、箱、盘安装垂直度允许偏差为0.15%，相互间接缝应不大于2mm，相邻两盘边的盘面偏差小于1mm。④线间和线对地间绝缘电阻值，馈电线路必须大于0.5MΩ，二次回路必须大于1MΩ。⑤带电体裸露载流部分之间或其与金属体之间电气间隙应符合规范要求。⑥柜、箱应有可靠的电击保护，柜内保护导体最小截面积Sp应根据电源进线相线截面积S决定，当S在35～400mm2时，Sp应不小于S\u002F2，且材质与其相同。⑦箱、盘安装应牢固，底边距地面为1.5m，照明配电板底边距地面不小于1.8m。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（交通）","建筑工程",0]