[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-903418":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},903418,584,1,"单选题","下列关于不间断电源UPS安装要求说法错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","不间断电源的输入应符合设计要求",false,{"key":16,"text":17,"correct":14},"B","不间断电源输出端的中线必须做重复接地",{"key":19,"text":20,"correct":21},"C","各连线的线对地间绝缘电阻值应大于1MΩ",true,{"key":23,"text":24,"correct":14},"D","安装时水平度、垂直度允许偏差不应大于0.15%","不间断电源UPS的安装要求包括：①不间断电源的输入、输出各级保护系统和输出电压稳定性、波形畸变系数、频率、相位、静态开关的动作等各项技术性能指标试验调整必须符合产品技术文件要求，且符合设计文件要求。②各连线的线间、线对地间绝缘电阻值应大于0.5MΩ。③不间断电源输出端的中线（N极），必须与由接地装置直接引来的地线干线相连接，做重复接地。④安装时应横平竖直，水平度、垂直度允许偏差不应大于0.15%。⑤主回路与控制回路应分别穿保护管敷设；在电缆支架上平行敷设应保持150mm距离。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（交通）","建筑工程",0]