[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-903408":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},903408,584,1,"单选题","下列关于配电工程中塑料管敷设要求说法错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","塑料管必须由阻燃处理的材料制成",false,{"key":16,"text":17,"correct":14},"B","塑料管不应敷设在易受机械损伤的场所",{"key":19,"text":20,"correct":14},"C","塑料管敷设时其温度不宜低于－15℃",{"key":22,"text":23,"correct":24},"D","采用套管连接时，套管长度宜为管外径的1.5～2倍",true,"配电工程中塑料管敷设要求包括：①塑料管及其配件必须由阻燃处理的材料制成，不应敷设在高温和易受机械损伤的场所。②管口应平整、光滑，管与管、管与盒（箱）等器件应采用插入法涂专用胶合剂连接；当采用套管连接时。套管长度宜为管外径的1.5～3倍。③塑料管直埋于现浇混凝土内时，应采取防止发生机械损伤的措施，敷设时其温度不宜低于－15℃。④暗配时与建筑物、构筑物表面距离不应小于15mm。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（交通）","建筑工程",0]