[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-903394":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},903394,584,1,"单选题","下列关于配电工程中钢管敷设要求说法正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","明配钢管与盒（箱）连接应采用螺纹连接",false,{"key":16,"text":17,"correct":18},"B","镀锌钢管和薄壁钢管应采用螺纹连接或套管紧定螺钉连接",true,{"key":20,"text":21,"correct":14},"C","钢管的内壁、外壁不必做防腐处理",{"key":23,"text":24,"correct":14},"D","潮湿场所和直埋于地下时应采用薄壁钢管","配电工程中钢管敷设要求包括：①潮湿场所和直埋于地下时应采用厚壁钢管，干燥场所应采用薄壁钢管。②钢管的内壁、外壁均应做防腐处理。钢管不应有折扁和裂缝，管内应无铁屑及毛刺，切断口应平整，管口应光滑。③镀锌钢管和薄壁钢管应采用螺纹连接或套管紧定螺钉连接。④明配钢管或暗配镀锌钢管与盒（箱）连接应采用锁紧螺母或护套帽固定，与设备连接时，应敷设到设备的接线盒内，管口与地面的距离宜大于200mm。⑤镀锌钢管的跨接地线连接宜采用专用接地线卡跨接。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（交通）","建筑工程",0]