[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902519":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902519,583,2,"多选题","对于架空线路的敷设，说法正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","靠近混凝土杆的两根架空导线间距不小于300mm",false,{"key":16,"text":17,"correct":18},"B","通信电缆与电力线的垂直距离不小于1.5m",true,{"key":20,"text":21,"correct":18},"C","低压电杆杆距宜在30?45m",{"key":23,"text":24,"correct":18},"D","低压电源架空引入线应采用≥4m ㎡的绝缘导线","BCD","教材p361。架空线路的敷设。架空导线间距不小于300mm，靠近混凝土杆的两根导线间距不小于500mm。上下两层横担间距：直线杆时为600mm；转角杆时为300mm。广播线、通信电缆与电力同杆架设时应在电力线下方，二者垂直距离不小于1.5m。低压电杆杆距宜在30?45m。三相四线制低压架空线路，在终端杆处应将保护线作重复接地，接地电阻不大于10n。当与引入线处重复接地点的距离小于500mm 时，可以不做重复接地。低压电源架空引入线应采用绝缘导线，其截面宜大于或等于4m ㎡。档距不宜大于25m,进线处对地距离不应低于2.7m。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]