[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902517":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902517,583,2,"多选题","与隔离开关不同的是，高压负荷开关（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","有明显可见的断开间隙",false,{"key":16,"text":17,"correct":18},"B","有简单的灭弧装置",true,{"key":20,"text":21,"correct":18},"C","能带负荷操作",{"key":23,"text":24,"correct":18},"D","适用于无油化、不检修、要求频繁操作的场所","BCD","教材p353。高压隔离开关。主要功能是隔离高压电源，以保证其他设备和线路的检修。其结构特点是断开后有明显可见的断开间隙，而且断开间隙的绝缘及相间绝缘是足够可靠的。高压隔离开关没有专门的灭弧装置，不允许带负荷操作。它可用来通断一定的小电流，如励磁电流不超过2A 的空载变压器、电容电流不超过5A 的空载线路以及电压互感器和避雷器等。高压负荷开关与隔离开关一样，具有明显可见的断开间隙。不同的是，高压负荷开关具有简单的灭弧装置，能通断一定的负荷电流和过负荷电流，但不能断开短路电流。高压负荷开关适用于无油化、不检修、要求频繁操作的场所。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]