[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902508":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902508,583,2,"多选题","在防雷接地系统中，符合安装要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","引下线可采用扁钢和圆钢敷设",true,{"key":16,"text":17,"correct":18},"B","引下线沿外墙明敷时断接卡子宜在距地300?400mm",false,{"key":20,"text":21,"correct":14},"C","当建筑物高度超过30m 时，30m 以上设置均压环",{"key":23,"text":24,"correct":18},"D","均压环均为扁钢","AC","教材p366。引下线可采用扁钢和圆钢敷设，也可利用建筑物内的金属体。单独敷设时，必须采用镀锌制品。引下线沿外墙明敷时，宜在离地面1.5?1.8m 处加断接卡子。暗敷时，断接卡可设在距地300?400mm 的墙内的接地端子测试箱内。均压环是高层建筑为防侧击雷而设计的水平避雷带。（1）当建筑物高度超过30m 时，30m 以上设置均压环。建筑物层高小于或等于3m 的每两层设置一圈均压环，层高大于3m 的每层设置一圈均压环。（2）均压环可利用建筑物圈梁的两条水平主钢筋，圈梁的主钢筋小于￠12mm 的，可用其四根水平主钢筋。用作均压环的圈梁钢筋应用同规格的圆钢接地焊接。没有圈梁的可敷设40mm×4mm 扁钢作为均压环。（3）用作均压环的圈梁钢筋或扁钢应与避雷引下线连接形成闭合回路。（4）建筑物30m 以上的金属门窗、栏杆等应用￠10mm 圆钢或25mm×4mm 扁钢与均压环连接。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]