[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902471":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902471,583,2,"多选题","对于气柜安装质量检验，说法正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","气柜壁板的对接焊缝均应进行真空试漏法",false,{"key":16,"text":17,"correct":14},"B","气柜底板的严密性试验均应经煤油渗透试验",{"key":19,"text":20,"correct":21},"C","下水封的焊缝应进行注水试验",true,{"key":23,"text":24,"correct":21},"D","钟罩、中节的气密试验和快速升降试验属于总体试验","CD","教材p341。 （1）气柜施工过程中的焊接质量检验。焊接规范要求： 1）气柜壁板所有对焊焊缝均应经煤油渗透试验。 2）下水封的焊缝应进行注水试验。 （2）气柜底板的严密性试验。可采用真空试漏法或氨气渗漏法。 （3）气柜总体试验。 1）气柜施工完毕，进行注水试验。其目的一是预压基础，二是检查水槽的焊接质量。水槽注水试验不应少于24h。 2）钟罩、中节的气密试验和快速升降试验。目的是检查各中节、钟罩在升降时的性能和各导轮、导轨、配合及工作情况、整体气柜密封的性能。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]