[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902453":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902453,583,2,"多选题","有关采暖管道安装，符合要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","管径大于32mm 宜采用焊接或法兰连接",true,{"key":16,"text":17,"correct":14},"B","共用立管宜采用热镀锌钢管螺纹连接",{"key":19,"text":20,"correct":21},"C","管道穿外墙或基础时应加设填料套管",false,{"key":23,"text":24,"correct":14},"D","一对共用立管每层连接的户数不宜大于三户","ABD","教材p244。 采暖管道安装要求： 2）管径大于32mm 宜采用焊接或法兰连接。 3） 热水采暖和汽、水同向流动的蒸汽和凝结水管道，坡度一般为3‰ ；汽、水逆向流动的蒸汽管道，坡度不得小于5‰ 。 4）管道最高点安装排气装置，最低点安装泄水装置。 5）管道穿过墙或楼板，应设置填料套管。穿外墙或基础时，应加设防水套管。套管直径比管道直径大两号为宜。 管道穿过厨房、卫生间等容易积水的房间楼板，应加设填料套管。 供回水干管的共用立管宜采用热镀锌钢管螺纹连接。一对共用立管每层连接户数不宜大于三户。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]