[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902444":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902444,583,2,"多选题","对于高压管道安装，说法正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","高压阀门应逐个进行强度和严密性试验",true,{"key":16,"text":17,"correct":14},"B","高压管道中心线弯曲半径R>5D（管道外径）",{"key":19,"text":20,"correct":14},"C","奥氏体不锈钢高压管热处理次数不得超过3 次",{"key":22,"text":23,"correct":24},"D","壁厚为16～34mm 的高压钢管采用V 型坡口",false,"ABC","教材p310。高压阀门应逐个进行强度和严密性试验。强度试验压力等于阀门公称压力的1.5 倍，严密性试验压力等于公称压力。高压管子应尽量冷弯，冷弯后可不进行热处理。奥氏体不锈钢管热弯时，加热温度以900～1000℃为宜。热弯后须整体进行固溶淬火处理。同时，取同批管子试样2 件，做晶间腐蚀倾向试验。如有不合格者，则全部作热处理。但热处理不得超过3 次。高压管道的焊缝坡口应采用机械方法。当壁厚小于16mm 时，采用V 型坡口；壁厚为7～34mm 时，可采用V 型坡口或U 型坡口。高压管道中心线弯曲半径及最小直边长度L 应符合要求：R>5D（管道外径L>1.3D（但不大于60mm）。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]