[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902322":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902322,583,2,"多选题","高层建筑采用临时高压给水系统时，说法正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","应设高位消防水箱并保证最不利点消火栓静水压力",true,{"key":16,"text":17,"correct":18},"B","发生火灾后由消防泵供给的水必须进入消防水箱",false,{"key":20,"text":21,"correct":18},"C","建筑高度超过100m 时的最不利点消火栓静水压力不应低于0.07MPa",{"key":23,"text":24,"correct":14},"D","不能满足静水压力要求时应设增压设施","AD","教材p173-174。高层建筑采用高压给水系统可不设高位消防水箱；采用临时高压给水系统应设高位消防水箱，水箱的设置高度应保证最不利点消火栓静水压力。当建筑高度不超过100m，最不利点消火栓静水压力不应低于0.07MPa；当建筑高度超过100m，不应低于0.15MPa。不能满足要求时，应设增压设施。消防水箱应储存10min 的消防用水量。除串联消防给水系统外，发生火灾后由消防泵供给的水不应进入消防水箱。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]