[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902321":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902321,583,2,"多选题","下列室内消火栓给水系统应设置消防水泵接合器的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","四层工业建筑",false,{"key":16,"text":17,"correct":14},"B","超过2 层或建筑面积大于10000 ㎡的地上建筑",{"key":19,"text":20,"correct":21},"C","高层民用建筑",true,{"key":23,"text":24,"correct":21},"D","室内消火栓设计流量大于10L\u002Fs 平战结合的人防工程","CD","教材p173。 下列场所的室内消火栓给水系统应设置消防水泵接合器： 1）高层民用建筑； 2）设有消防给水的住宅、超过五层的其他多层民用建筑； 3）超过2 层或建筑面积大于10000 ㎡的地下或半地下建筑、室内消火栓设计流量大于l0L\u002Fs 平战结合的人防工程； 4）高层工业建筑和超过四层的多层工业建筑； 5）城市交通隧道。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]