[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-902308":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},902308,583,2,"多选题","同一泵组的消防水泵设置正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防水泵型号宜一致",true,{"key":16,"text":17,"correct":18},"B","工作泵不少于3 台",false,{"key":20,"text":21,"correct":14},"C","消防水泵的吸水管不应少于2 条",{"key":23,"text":24,"correct":14},"D","消防水泵的出水管上应安装止回阀和压力表","ACD","教材p174。一组消防水泵由工作泵和备用泵组成。同一泵组消防水泵型号宜一致，且工作泵不宜超过3 台。消防水泵应采用自灌式吸水；从市政管网直接抽水时，应在消防水泵出水管上设置倒流防止器。一组消防水泵的吸水管不应少于2 条；临时高压消防给水系统应采用防止消防水泵低流量空转过热的技术措施。当设计无要求时，消防水泵的出水管上应安装止回阀和压力表；消防水泵泵组的总出水管上还应安装压力表和泄压阀。安装压力表时应加设缓冲装置。压力表和缓冲装置之间应安装旋塞；压力表量程应为工作压力的2?2.5 倍。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]