[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-901916":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},901916,583,2,"多选题","(2018年)按《1kV 及以下配线工程施工与验收规范》（GB 50575－2010）的规定，下列电气配管钢导管敷设连接符合要求的有（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","暗配钢导管与盒（箱）连接可采用焊接",false,{"key":16,"text":17,"correct":18},"B","明配钢导管与盒（箱）连接可采用螺纹连接",true,{"key":20,"text":21,"correct":18},"C","可将钢导管敷设到设备接线盒内，实现与用电设备直接连接",{"key":23,"text":24,"correct":18},"D","钢导管宜经柔性导管过渡与用电设备接线盒间接连接","BCD","1）暗配的非镀锌钢导管与盒（箱）连接可采用焊接连接；2）明配的钢导管或暗配的镀锌钢导管与盒（箱）连接均应采用螺纹连接，用锁紧螺母进行连接固定；3）钢导管与用电设备直接连接时，宜将导管敷设到设备的接线盒内。4）钢导管与用电设备间接连接时，宜经可弯曲导管或柔性导管过渡。",{"id":6,"name":28,"category":29,"favorite":30},"建设工程技术与计量（安装)","建筑工程",0]