[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-901659":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},901659,583,1,"单选题","（2020年真题）关于吊扇、壁扇的安装，符合要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","吊扇挂钩直径不应小于吊扇挂销直径",true,{"key":16,"text":17,"correct":18},"B","吊扇组装可以根据现场情况改变扇叶的角度",false,{"key":20,"text":21,"correct":18},"C","无专人管理场所的换气扇不设置定时开关",{"key":23,"text":24,"correct":18},"D","壁扇底座不可采用膨胀螺栓固定","P190-199 吊扇挂钩安装应牢固，吊扇挂钩的直径不应小于吊扇挂销直径，且不应小于8mm;挂钩销钉应有防振橡胶垫;挂销的防松零件应齐全、可靠。 吊扇组装不应改变扇叶角度,扇叶的固定螺栓防松零件应齐全。 换气扇安装应紧贴饰面、固定可靠。无专人管理场所的换气扇宜设置定时开关。 壁扇底座应采用膨胀螺栓或焊接固定，固定应牢固可靠;膨胀螺栓的数量不应小于3个，且直径不应小于8mm。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]