[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-901415":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},901415,583,1,"单选题","漏电保护器安装符合要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","照明线路的中性线不得通过漏电保护器",false,{"key":16,"text":17,"correct":18},"B","安装后应带负荷分、合开关三次，不得出现误动作",true,{"key":20,"text":21,"correct":14},"C","安装漏电保护器后应拆除单相闸刀开关或瓷插",{"key":23,"text":24,"correct":14},"D","电源进线必须接在漏电保护器的正下方","教材p359。（1）漏电保护器应安装在进户线小配电盘上或照明配电箱内。安装在电度表之后，熔断器（或胶盖刀闸）之前。对于电磁式漏电保护器，也可装于熔断器之后。（2）所有照明线路导线，包括中性线在内，均须通过漏电保护器。（3）电源进线必须接在漏电保护器的正上方，出线均接在下方。（4）安装漏电保护器后，不能拆除单相闸刀开关或瓷插、熔丝盒等。（6）漏电保护器在安装后带负荷分、合开关三次，不得出现误动作；再用试验按钮试验三次，应能正确动作（即自动跳闸，负载断电）。（7）运行中的漏电保护器，每月至少用试验按钮试验一次。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]