[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-901319":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},901319,583,1,"单选题","热力管道安装符合要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","蒸汽支管应从主管下部或侧面接出",false,{"key":16,"text":17,"correct":14},"B","输送蒸汽的水平管道变径时应采用偏心异径管并取管顶平",{"key":19,"text":20,"correct":14},"C","蒸汽管道敷设在其前进方向的左侧，凝结水管道敷设在右侧",{"key":22,"text":23,"correct":24},"D","减压阀应垂直安装在水平管道上",true,"教材p297。（1）热力管道应设有坡度，汽、水同向流动的蒸汽管道坡度一般为3‰，汽、水逆向流动时坡度不得小于5‰。热水管道应有不小于2‰的坡度，坡向放水装置。（2）蒸汽支管应从主管上方或侧面接出，热水管应从主管下部或侧面接出。（3）水平管道变径时应采用偏心异径管连接，当输送介质为蒸汽时，取管底平以利排水；输送介质为热水时，取管顶平，以利排气。（4）蒸汽管道一般敷设在其前进方向的右侧，凝结水管道敷设在左侧。热水管道敷设在右侧，而回水管道敷设在左侧。（6）直接埋地热力管道穿越铁路、公路时交角不小于45°，管顶距铁路轨面不小于1.2m，距道路路面不小于0.7m，并应加设套管，套管伸出铁路路基和道路边缘不应小于1m。（7）减。压减阀压应阀垂组直一安般装设在在水离平地管面道上1.2m 处，如设在离地面 3m 左右处时，应设置永久性操作平台。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]