[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-901192":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},901192,583,1,"单选题","送风温度低于室温，出风速度较低，送风气流与室内气流掺混量最小，且能够保存分区流态的通风方式为()。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","单向流通风",false,{"key":16,"text":17,"correct":14},"B","均匀流通风",{"key":19,"text":20,"correct":14},"C","稀释通风",{"key":22,"text":23,"correct":24},"D","置换通风",true,"2020版教材P260 本题考点是全面通风的种类。本知识点要求考生重点掌握。 置换通风的送风分布器通常都是靠近地板，送风口面积大，出风速度低(一般低于0.5m\u002Fs) 。置换通风用于夏季降温时，送风温度通常低于室内温度2~4℃。低速、低温送风与室内分区流态是置换通风的重要特点。置换通风对送风的空气分布器要求较高，它要求分布器能将低温的新风以较小的风速均匀送出，并能散布开来。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]