[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-901141":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},901141,583,1,"单选题","符合导管敷设规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","暗配的导管表面埋设深度不应小于10mm",false,{"key":16,"text":17,"correct":18},"B","导管穿越外墙时应设置防水套管",true,{"key":20,"text":21,"correct":14},"C","导管在蒸气管上面时距离为0.5m",{"key":23,"text":24,"correct":14},"D","进入配电柜的导管管口应高出柜基础面20mm","教材p210。 （1）暗配的导管表面埋设深度与建筑物、构筑物表面的距离不应小于15mm。 （2）进入配电（控制）柜、台、箱内的导管管口，当箱底无封板时，管口应高出柜、台、箱、盘的基础面50?80mm。 （3）导管穿越外墙时应设置防水套管。 （6）导管与热水管、蒸汽管平行敷设时，宜敷设在热水管、蒸汽管的下面，当有困难时，可敷设在其上面；相互间的最小距离宜符合表4.4.4 规定。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]