[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-901126":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},901126,583,1,"单选题","对于水流指示器安装，说法正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","在管道试压和冲洗前安装",false,{"key":16,"text":17,"correct":14},"B","信号阀应安装在水流指示器后的管道上",{"key":19,"text":20,"correct":14},"C","水流指示器前后应保持不宜小于300mm 直管段",{"key":22,"text":23,"correct":24},"D","电器元件部位竖直安装在水平管道上侧",true,"教材p179。 （5）水流指示器安装 1） 应在管道试压和冲洗合格后进行。 2） 一般安装在每层的水平分支干管或某区域的分支干管上；应使电器元件部位竖直安装在水平管道上侧，倾斜度不宜过大，其动作方向应和水流方向一致；安装后的水流指示器不应与管壁发生碰擦；水流指示器前后应保持有5倍安装管径长度的直管段。 3）信号阀应安装在水流指示器前的管道上，与水流指示器的距离不宜小于300mm。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]