[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-900667":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},900667,583,1,"单选题","硬聚氯乙烯给水管（PVC-U），当管外径De≥63mm 时，宜采用的连接方式为（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","承插式粘接",false,{"key":16,"text":17,"correct":14},"B","螺纹连接",{"key":19,"text":20,"correct":21},"C","承插式弹性橡胶密封圈柔性连接",true,{"key":23,"text":24,"correct":14},"D","承插焊接","硬聚氯乙烯给水管（PVC-U）：适用于给水温度不大于 45℃、给水系统工作压力不大于 0.6MPa 的生活给水系统。高层建筑的加压泵房内不宜采用 PVC-U 给水管；水箱的进出水管、排污管、自水箱至阀门间的管道不得采用塑料管；公共建筑、车间内塑料管长度大于 20m 时应设伸缩节。PVC-U 给水管宜采用承插式粘接、承插式弹性橡胶密封圈柔性连接和过渡性连接。管外径 De＜63mm 时，宜采用承插式粘接连接；管外径 De≥63mm 时，宜采用承插式弹性橡胶密封圈柔性连接；与其他金属管材、阀门、器具配件等连接时，采用过渡性连接，包括螺纹或法兰连接。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]