[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-900349":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},900349,583,1,"单选题","(2018年)下列关于喷水灭火系统喷头的安装，正确的说法是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","当喷头公称通径大于10mm 时，应在配水管上安装过滤器",false,{"key":16,"text":17,"correct":14},"B","在系统管道冲洗试压前安装",{"key":19,"text":20,"correct":21},"C","不得对喷头进行拆装和附加任何装饰性涂层",true,{"key":23,"text":24,"correct":14},"D","当通风管道宽度大于1.0m 时，喷头应安装在其腹面以下部位","（3）喷头安装1）喷头应在系统管道试压、冲洗合格后安装， 喷头安装时不得对喷头进行拆装、改动，喷头上不得附加任何装饰性涂层。2）当喷头的公称通径小于10mm 时，应在配水干管或配水管上安装过滤器。3）喷头安装时，溅水盘与吊顶、门、窗、洞口或墙面的距离应符合设计要求。当喷头溅水盘高于附近梁底或宽度小于1.2m 的通风管道腹面时，喷头溅水盘高于梁底、通风管道腹面的最大垂直距离应符合有关规定。当通风管道宽度大于1.2m 时，喷头应安装在其腹面以下部位。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]