[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-900248":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},900248,583,1,"单选题","(2018年)管道进行水压试验时，符合管道水压试验要求的操作是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","注水前应排尽管道内空气，向管道注水时不要打开排气阀",false,{"key":16,"text":17,"correct":14},"B","管道注满水后立即升压至规定的试验压力",{"key":19,"text":20,"correct":14},"C","试验合格的管道先打开排水阀进行排水，再打开排气阀",{"key":22,"text":23,"correct":24},"D","试验时，当环境温度低于5℃时，应采取防冻措施",true,"管道水压试验的方法和要求：（2）注入液体时应排尽空气。向管内注水时要打开排气阀，当发现管道末端的排气阀流水时，立即把排气阀关好，等全系统管道最高点的排气阀见到流水时，说明水已经注满，把最高点的排气阀关好。对管道进行检查，如没有明显的漏水现象就可升压。升压时应缓慢进行，达到规定的试验压力以后，稳压10min，经检查无泄漏无变形为合格。（3）试验合格的管道要把管道内的水放掉，放水以前先打开管道最高点的排气阀，再打开排水阀，把水放入排水管道。最后拆除试验用临时管道、连通管及盲板，拆下的阀门及仪表复位，填写好管道系统试验记录。（4）试验时，环境温度不宜低于5℃。当环境温度低于5℃时，应采取防冻措施。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]