[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-900217":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},900217,583,1,"单选题","(2017年)下列关于喷水灭火系统的报警阀组安装，正确的说法是()。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","先安装辅助管道，后进行报警阀组的安装",false,{"key":16,"text":17,"correct":18},"B","报警阀组与配水干管的连接应使水流方向一致",true,{"key":20,"text":21,"correct":14},"C","当设计无要求时，报警阀组安装高度宜为距室内地面0.5m",{"key":23,"text":24,"correct":14},"D","报警阀组安装完毕，应进行系统试压冲洗","(4）报警阀组安装。应在供水管网试压、冲洗合格后进行。安装时应先安装水源控制阀、报警阀，然后进行报警阀辅助管道的连接，水源控制阅、报警阅与配水干管的连接应使水流方向一致。报警阀组安装的位置应符合设计要求；当设计元要求时，报警阀组应安装在便于操作的明显位置，距室内地面高度宜为1.2m，两侧与墙的距离不应小于0.5m，正面与墙的距离不应小于1.2m；报警阀组凸出部位之间的距离不应小于0.5m。安装报警阀组的室内地面应有排水设施。",{"id":6,"name":27,"category":28,"favorite":29},"建设工程技术与计量（安装)","建筑工程",0]