[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-892184":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},892184,577,2,"多选题","配线保护管遇到下列（ ）情况时，应增设管路接线盒和拉线盒。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","管长度每超过30m，无弯曲",true,{"key":16,"text":17,"correct":14},"B","管长度每大于20m，有1个弯曲",{"key":19,"text":20,"correct":14},"C","管长度每大于15m，有2个弯曲",{"key":22,"text":23,"correct":24},"D","管长度每大于10m，有3个弯曲",false,{"key":26,"text":27,"correct":14},"E","管长度每大于8m，有3个弯曲","ABCE","知识点:建筑电气项目计量规则。配线保护管遇到下列情况之一时，应增设管路接线盒和拉线盒：管长度每超过30m，无弯曲；管长度每大于20m，有1个弯曲；管长度每大于15 m，有2个弯曲；管长度每大于8m，有3个弯曲。参见教材P246。",{"id":6,"name":31,"category":32,"favorite":33},"[安装工程]建设工程计量与计价实务","建筑工程",0]