[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-891833":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},891833,577,2,"多选题","配线保护管需增设管路接线盒和拉线盒的情况有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","导管长度每大于20m，有2个弯曲",true,{"key":16,"text":17,"correct":14},"B","导管长度每大于30m，有1个弯曲",{"key":19,"text":20,"correct":21},"C","导管长度每大于5m，有4个弯曲",false,{"key":23,"text":24,"correct":14},"D","导管长度每大于10m，有3个弯曲",{"key":26,"text":27,"correct":21},"E","导管长度每大于40m，有1个弯曲","ABD","配线保护管遇到下列情况之一时，应增设管路接线盒和拉线盒：①导管长度每大于40m，无弯曲；②导管长度每大于30m，有1个弯曲；③导管长度每大于20m，有2个弯曲；④导管长度每大于10m，有3个弯曲。",{"id":6,"name":31,"category":32,"favorite":33},"[安装工程]建设工程计量与计价实务","建筑工程",0]