[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-891667":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},891667,577,2,"多选题","管道安装完毕后，要通过致密性试验检验其安装质量，其试验压力分别为（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","在水压试验中，承受内压的地上钢管道及有色金属管道的试验压力为设计压力的1.5倍",true,{"key":16,"text":17,"correct":18},"B","真空管道的试验压力应为0.4MPa",false,{"key":20,"text":21,"correct":14},"C","在气压试验中，承受内压钢管及有色金属管的气压试验压力为设计压力的1.15倍",{"key":23,"text":24,"correct":14},"D","在气压试验中，真空管道的试验压力应为0.2MPa",{"key":26,"text":27,"correct":18},"E","埋地钢管道的试验压力应为设计压力的1倍","ACD","在水压试验中，承受内压的地上钢管道及有色金属管道的试验压力应为设计压力的1.5倍。埋地钢管道的试验压力应为设计压力的1.5倍，并不得低于0.4MPa。在气压试验中，承受内压钢管及有色金属管的强度试验压力应为设计压力的1.15倍；真空管道的试验压力应为0.2MPa。",{"id":6,"name":31,"category":32,"favorite":33},"[安装工程]建设工程计量与计价实务","建筑工程",0]