[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-890710":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},890710,577,1,"单选题","从技术和经济角度考虑，在人行频繁、非机动车辆通行的地方敷设热力管道，宜采用的敷设方式为（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","地面敷设",false,{"key":16,"text":17,"correct":14},"B","低支架敷设",{"key":19,"text":20,"correct":21},"C","中支架敷设",true,{"key":23,"text":24,"correct":14},"D","高支架敷设","热力管道架空敷设按支架的高度不同，可分为低支架、中支架和高支架三种敷设形式。其中，中支架敷设在人行频繁，非机动车辆通行的地方采用。中支架敷设的管道保温结构底部距地面的净高为2.5～4.0m，支架一般采用钢筋混凝土现浇（或预制）或钢结构。低支架敷设是在不妨碍交通，不影响厂区扩建的地段可采用低支架敷设。高支架敷设是在管道跨越公路或铁路时采用，支架通常采用钢结构或钢筋混凝土结构，高支架敷设的管道保温结构底部距地面的净高为4.5～6.0m。",{"id":6,"name":27,"category":28,"favorite":29},"[安装工程]建设工程计量与计价实务","建筑工程",0]