[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-881852":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},881852,569,2,"多选题","某办公建筑采用风机盘管十新风的集中空气调节系统，冷源为离心式冷水机组，夏季室内设计温度t=26℃，冷水供／回水设计温度为12\u002F17℃，下列哪几项说法是错误的？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","选用冷水供／回水温度为7\u002F12℃的机组，在设备中表明供／回水设计温度为12\u002F17℃的要求",false,{"key":16,"text":17,"correct":14},"B","采用常规风机盘管，同等风量，同等水量，同等阻力条件下，其传热系数保持不变",{"key":19,"text":20,"correct":21},"C","采用常规风机盘管，同等风量条件下，其输出冷量保持不变",true,{"key":23,"text":24,"correct":21},"D","同等冷量条件下，冷水供／回设计温度为12\u002F17℃的系统较7\u002F12℃的系统，所需水泵功率明显下降","CD","设计冷水供回水温差保持不变时，水流量不变，但供回水温度提高，传热系数不变。但水量不同时，输出冷量将不同。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]